This is supplementary to the Elevate 6 manual, and summarizes the operation of the auto mode provided for use with the "Group Collective" Dispatcher.
When a car leaves the Home floor, the dispatcher tests if the load exceeds the Load switch detection level (%). The Up peak detection counter is incremented by 1 when a car leaves with a load above the Load switch detection level and is decremented if the load is below that level. When the counter reaches the On level, the up peak program is switched on. A blocking system ensures that the up peak detection counter does not exceed the On level.
If the up peak program is on, the Clock inhibit timer decrements the Up peak detection counter by 1 at fixed time intervals, as defined by the Clock rate. When the up peak detection counter reaches the Clock inhibit level, the Clock inhibit timer is switched off.
When the Up peak detection counter reaches the Off level (always set at 1), the up peak program is turned off.
Operates as per the up peak detection system, except that the load is measured as the car arrives at the home floor; the down peak as opposed to up peak program is initiated.